Practice the EPA 608 Type 3 section for low-pressure appliances such as centrifugal chillers. 25 questions, 18 correct to pass, every answer explained, with no signup.
Type 3 · Question 1 of 25
See the answer after each questionNo answers until you finish, like the real exam
1. Technicians servicing low-pressure appliances must hold Type III certification or Universal certification. (True or false)
2. High head pressure on a low-pressure system can indicate air in the system and possible purge-unit trouble. (True or false)
3. Excessive running of a purge system on a low-pressure chiller usually indicates a leaking system. (True or false)
4. Before recovering refrigerant from a chiller suspected of tube leaks, the water sides of the evaporator and condenser should be drained. (True or false)
5. Open-drive low-pressure refrigeration systems are particularly susceptible to leaks from the shaft seal. (True or false)
6. Most low-pressure appliances are used for comfort cooling. (True or false)
7. What is the preferred way to raise the pressure of a charged low-pressure chiller so it can be leak checked?
8. During vapor or liquid removal from a low pressure refrigeration system, which items should be on?
9. On a low-pressure chiller, which job counts as major maintenance, service, or repair under EPA rules?
10. Why are room sensors and alarms required in machinery rooms?
11. A purge unit pulls a mix of air, moisture, and refrigerant vapor off a low-pressure chiller, separates them, and vents the air. Where does the cleaned refrigerant go?
12. R-123 is the refrigerant in many low-pressure chillers. What is its ASHRAE Standard 34 safety group?
13. What is the ASHRAE safety rating of R-1233zd?
14. What is the boiling point of R-123?
15. What is the pressure of R-123 at 80°F on the PT chart?
16. What happens if a low-pressure appliance is pressurised above 15 psig?
17. Which of the following components are only found in Type 3 appliances?
18. Which of the following is not a Type 3 refrigerant?
19. Which of the following refrigerants would be used in a low-pressure appliance?
20. You've pressurized a chiller tube with colored water using a tube test kit. Which result confirms the tube is leaking?
21. With the water side drained, why is the drain valve opening the preferred spot to sample with a leak detector?
22. Continuous excessive moisture collection in which component of a low-pressure refrigeration system could indicate a leak?
23. After pulling a low-pressure chiller down to 1 mm Hg, the reading climbs to 2.7 mm Hg over a short hold. What is the compliant next step according to ASHRAE?
24. What is the maximum pressure of dry nitrogen that may be used to leak test a low-pressure chiller?
25. How does liquid water most often get into the refrigerant side of a low-pressure chiller?
26. A belt-driven non-hermetic compressor has sat idle for months and leaks on startup. What condition most likely explains the leakage?
27. A low-pressure chiller with a full charge over 200 lb is found leaking on June 15, 2024. The owner chooses to replace it with a system that uses a refrigerant exempt from the venting prohibition. By what date must the old unit be retired?
28. How long must owners and operators of low-pressure chillers using R11 refrigerant keep records of leak inspections, initial verification, and follow-up verification tests?
29. How long must owners and operators of regulated appliances normally containing 50 or more pounds of CFC refrigerant keep records of leak inspections, initial leak verification, and follow-up verification tests?
30. When disposing of an HVAC appliance with 10 pounds of refrigerant, what is one EPA-mandated recordkeeping requirement?
31. Why do recovery units used on low-pressure chillers have a high-pressure cut-out set at about 10 psig?
32. You're beginning recovery on a low-pressure chiller at ambient conditions. To follow best practice, you should:
33. Why use a water-cooled recovery unit?
34. In the case of confirmed leaks during refrigerant recovery in a chiller, what must be done?
35. Recovery or recycling equipment for use on chillers that was manufactured or imported on or after November 15, 1993 must have which of these?
36. While evacuating a low-pressure chiller with no confirmed tube leaks, the water pump is accidentally switched off. As recovery continues, the barrel temperature keeps dropping. What is the immediate risk if you do not restore water circulation?
37. When charging an evacuated low-pressure chiller, why is vapour added before liquid?
38. While charging a water-cooled, low-pressure chiller after evacuation, which indicator tells you it's safe to switch from vapor to liquid charging?
39. Identify the recovery requirements for equipment disposal
40. Water present in the system can freeze if?
41. To introduce initial refrigerant vapor from the lowest point on a centrifugal chiller, which service connection should be used?
42. During the evacuation of a moisture-laden chiller, the vacuum stalls, and frost begins to form in the piping. What action should the technician take to restore flow without adding refrigerant?
43. After confirming a leak, a technician is scheduled to replace an evaporator coil on a low-pressure chiller. Under EPA rules, this job is classified as a:
44. A mechanical room contains equipment using A1, A2L, and B2 refrigerants. To comply with ASHRAE Standard 15-2013, the refrigerant alarm system must detect leaks from:
45. According to ASHRAE Standard 15-2013, which equipment is mandated to detect refrigerant leaks?
46. During a design review, a junior technician proposes installing two pressure relief valves in series on the discharge line “for extra safety.”The correct response is:
47. What is the main function of isopropyl alcohol in refrigeration systems?
48. If a unit experiences a compressor burnout, we would collect an ____ as part of a ____.
49. Why do low-pressure chillers require purge units?
50. What is the primary purpose of a purge unit on a low-pressure chiller?
50 free Type 3 practice questions with instant scoring
This EPA 608 Type 3 practice test draws 25 of the 50 questions each time and scores them instantly. Practice mode shows the answer and explanation after each question; Exam mode holds your score until you finish, like the real Type 3 section.
Sources only. Not affiliated with or endorsed by EPA.
Type 3 exam questions, answered
These are the Type 3 questions technicians search for most, each answered in a few lines with the rule behind it.
Where does refrigerant removal from a low-pressure system start?
With the liquid. Pump the liquid refrigerant out first, then recover the remaining vapor down to 25 mm Hg absolute. During removal, circulate the chiller's water or drain it to prevent freezing.
Source: §82.156(a), Table 1; EPA 608 Test Topics, Type 3.
Which part of an open-drive low-pressure chiller is most likely to leak?
The shaft seal. In an open-drive compressor the shaft passes out through the housing to an external motor, and the seal around it is a common leak point. A low-pressure chiller runs below atmospheric pressure, so a leak there lets air in rather than letting refrigerant out.
What does excessive purge run time on a low-pressure chiller mean?
It is a sign of a leak. EPA lists excessive purging as a sign of leakage into a low-pressure system: the chiller runs below atmospheric pressure, so air leaks in, and the purge unit runs longer to remove it.
Source: EPA 608 Test Topics, Type 3.
How do you leak check a low-pressure chiller?
Raise its pressure first, usually by circulating hot water through the tubes or using a built-in heating or pressurization device (such as a Prevac), so a leak pushes refrigerant out where a detector can find it. If the chiller has been emptied, pressurize it with dry nitrogen at no more than 10 psig, because the rupture disc bursts at 15 psig.
Source: EPA 608 Test Topics, Type 3 (order of preference; maximum leak test pressure).
Why do low-pressure chillers need a purge unit?
Because they operate below atmospheric pressure. Any leak lets air and moisture into the refrigerant circuit instead of letting refrigerant out, and the purge unit removes those non-condensables (air and moisture).
The questions follow EPA's Type 3 test topics. A linked topic opens its answer in the exam questions tab, and the EPA 608 cheat sheet has every number on one page.
Purge units, the rupture disc and low-pressure refrigerants such as R-123.
Safety
Machine-room safety under ASHRAE 15 and the toxicity of R-123.
Passing the Type 3 section
Type 3 passes at 18 of 25 on the proctored, closed-book exam and certifies you for low-pressure appliances once you also pass Core. It is part of Universal certification, and certification never expires. Read what Type 3 certification covers.
EPA 608 Type 3 practice test FAQ
Is this EPA 608 Type 3 practice test free?
Yes. The 50 Type 3 questions on this page are free, with instant scoring and an explanation for every answer, and no signup. A free account adds the full question bank and saves your scores and score history.
What is Type 3 on the EPA 608 exam?
Type 3 covers low pressure appliances, mainly large centrifugal chillers running R-123 at or below atmospheric pressure, where a leak draws air in rather than releasing refrigerant. The EPA 608 practice test hub links every section.
What refrigerants do low pressure systems use?
R-123 is the main refrigerant in service and is still produced for servicing existing chillers until 2030; R-11 is fully phased out; R-1233zd is an HFO alternative with an A1 ASHRAE rating. All three operate below atmospheric pressure, which is what makes a system low pressure under Section 608.
Do you need Type 3 to repair an R-22 chiller?
No. An R-22 or R-410A chiller is a high pressure appliance, so the technician needs Type 2 or Universal certification. Type 3 applies only to low pressure equipment such as R-123 centrifugal chillers.