EPA 608 Type 1 Practice Test

The EPA 608 Type 1 practice test on this page is a free 50-question bank for the small appliance section. It covers the 5 pound rule, the 90% and 80% recovery thresholds, and passive recovery on factory sealed systems such as refrigerators and window units. Each attempt draws a random 25, scores it instantly against the 18 of 25 (72%) pass mark, and explains every answer.

Start the test Skip to: what the exam covers · the 5 pound rule · recovery levels · ESCO and the open book option · FAQ

50 free Type 1 practice questions with instant scoring

The 50 EPA 608 Type 1 practice questions below are drawn 25 at a time, scored instantly, and explained with the rule each answer comes from.

  1. 1. We need separate recovery cylinders for each class of refrigerants (e.g. HCFCs). For example, we cannot use the same cylinders to recover CFC and HCFC refrigerants. But we can use the same cylinder to recover different HCFC refrigerants. (True or false)

  2. 2. An active recovery machine is required for all systems. Passive recovery is a thing of the past. (True or false)

  3. 3. For both active recovery and passive recovery, we must recover 80% of the appliance charge if the compressor is not working. (True or false)

  4. 4. If a refrigerant's pressure readings are not stable, we can use its temperature readings to compare to its PT chart to check for noncondensables. (True or false)

  5. 5. Installing both high and low side access valves will increase recovery time. (True or false)

  6. 6. Low loss fittings are not only required during refrigerant recovery from appliances containing ODS and their substitutes, but also in other situations such as routine service and pressure checking. (True or false)

  7. 7. Defrost heaters: (Select all that apply)

  8. 8. What should we do to recover refrigerant from a system with a compressor that is not working? (Select all that apply)

  9. 9. Which of the following are types of low loss fittings? (Select all that apply)

  10. 10. Which of the following are needed to check for noncondensables in a system? (Select all that apply)

  11. 11. Which of these can be vented? (Select all that apply)

  12. 12. If a recovery device cannot achieve a 4-inch vacuum, which one of the following does it have to be able to do in order to be used with Type I small appliances? (Select all that apply)

  13. 13. Which features are part of the EPA definition of a small appliance? (Select all that apply)

  14. 14. Which methods are acceptable for monitoring that a recovery tank does not exceed 80% full? (Select all that apply)

  15. 15. A near azeotropic blend will contain:

  16. 16. A zeotropic blend will contain:

  17. 17. Access fittings:

  18. 18. If the compressor is not working and we are performing passive recovery, we need to take steps to do what?

  19. 19. If the pressure of the system is found to be 0 psig, can we recover refrigerant from the system?

  20. 20. If the pressure reading and expected pressure are far apart, which of the following are possibly contained in the refrigerant?

  21. 21. A sealed household refrigerator has a working compressor and a blocked capillary tube. To recover the charge, what access setup is required?

  22. 22. Solderless piercing valves:

  23. 23. What does system dependent recovery mean?

  24. 24. We can use a known refrigerant's PT chart to see if there are noncondensables in the refrigerant.

  25. 25. What is the approximate pressure of a storage container of R-22 that is stored at 75°F? Assume there are no impurities. PT Chart

  26. 26. What is the approximate pressure of a storage container of R-404a that is stored at 60°F? Assume there are no impurities. PT Chart

  27. 27. When performing active recovery and the compressor is working, we must recover to what levels?

  28. 28. Which method of monitoring fill level is the most accurate?

  29. 29. Which methods are approved by the EPA to monitor fill level of recovery cylinders?

  30. 30. You are servicing an appliance that contains R-134a. Which of the following can you use to recover the refrigerant?

  31. 31. Contaminated refrigerants can cause the appliance to:

  32. 32. According to EPA 608 retrofit guidelines, which refrigerant is approved for retrofitting certain low temperature R-22 systems, such as household freezers, when proper oil changes and system modifications are performed?

  33. 33. If we find refrigerant that is mixed, what should we do?

  34. 34. If we use nitrogen to pressurize a system or blow debris out (after fully recovering the refrigerant in the appliance), we can?

  35. 35. What is isobutane?

  36. 36. New household refrigerators and freezers can be factory charged with?

  37. 37. Small appliances include:

  38. 38. Up to how many pounds of refrigerant can Type I appliances contain?

  39. 39. Which of the following statements about hydrocarbons is NOT correct?

  40. 40. Which of the following is not true?

  41. 41. Which of the following statements is true about refrigerant recovery?

  42. 42. Which of the following refrigerants is not covered by the sales restriction of Section 608?

  43. 43. At high temperatures, what do CFCs and HCFCs decompose to?

  44. 44. Burning CFCs and HCFCs can:

  45. 45. If refrigerant has been released, what is the first thing you should do?

  46. 46. If a self contained breathing apparatus cannot be found, what should be done?

  47. 47. Safety markings used in appliances with hydrocarbon refrigerants are:

  48. 48. Why must technicians treat refrigerant cylinders as potential explosion hazards?

  49. 49. What piece of equipment is needed on nitrogen tanks when using them to service an appliance?

  50. 50. When do we need to use safety eyewear and butyl lined gloves?

What the Type 1 exam covers

Type 1 (Type I in older material) certification governs small appliances: factory sealed systems containing 5 lbs or less of refrigerant, such as domestic refrigerators, window air conditioners, PTAC units, vending machines, and water coolers. The 25-question section tests three areas:

How EPA defines a small appliance: 5 pounds or less, sealed at the factory

Under 40 CFR §82.152, a small appliance is any appliance fully manufactured, charged, and hermetically sealed in a factory with five pounds or less of refrigerant. The regulation names refrigerators and freezers, room air conditioners including window units and PTACs, packaged terminal heat pumps, dehumidifiers, under the counter ice makers, vending machines, and drinking water coolers. The threshold is the refrigerant charge, not the appliance weight: split system residential units usually hold more and fall under the EPA 608 Type 2 practice test; low pressure chillers on R-123 or R-11 fall under the EPA 608 Type 3 practice test.

Who needs Type 1. Any technician who handles refrigerant in small appliances must hold at least Type 1 under Section 608 of the Clean Air Act. Every candidate passes the 25-question Core section first, covered by the EPA 608 Core practice test; Core plus all three Types is Universal, the 100-question sitting the EPA 608 Universal practice test simulates.

Venting exemptions. The venting prohibition covers CFC, HCFC, and HFC refrigerants and their substitutes, so R-12, R-22, and R-134a may never be knowingly released. The Type 1 test asks the exempt substitutes as a select all question: ammonia (R-717), carbon dioxide (R-744), nitrogen (R-728), and water. Hydrocarbons such as R-600a and R-290 are exempt only in the end uses EPA has listed.

Type 1 recovery requirements: 90%, 80%, or 4 inches of mercury

Unlike Type 2 and Type 3, Type 1 recovery is set as a percentage of the refrigerant charge, with a 4 inch vacuum alternative. Under 40 CFR §82.156(h), the required amount depends on whether the appliance compressor is running and on the manufacture date of the recovery equipment. The EPA 608 Type 1 study guide explains where the numbers come from; the cheat sheet in the EPA 608 study guide puts every section's thresholds on one page.

Required recovery by compressor status and recovery equipment date

Required recovery for a small appliance is 90%, 80%, or 4 inches of mercury vacuum, set by compressor status and recovery equipment date.

Condition when you recover Required recovery
Compressor is operating (recovery equipment made on or after Nov 15, 1993) 90% of the charge
Compressor is not operating (recovery equipment made on or after Nov 15, 1993) 80% of the charge
Recovery equipment made before Nov 15, 1993, compressor operating or not 80% of the charge
Alternative for either case, evacuate the appliance 4 inches of mercury vacuum

Why 90% is the operating number. A running compressor pushes refrigerant out, so the operating compressor sets the higher bar (90%) and a dead compressor the lower one (80%); the rule is the same whether the recovery equipment is system dependent or self contained.

Self contained vs system dependent (passive) recovery

Self contained (active) recovery equipment has its own compressor or pump, so it pulls refrigerant out whether or not the appliance compressor runs. System dependent (passive) equipment has no pump of its own: it relies on the appliance compressor, or the pressure inside the sealed system, to push refrigerant into a recovery bag or cylinder. Under 40 CFR §82.158, system dependent equipment may only be used on appliances that normally hold 15 lbs or less of refrigerant. Both methods are held to the 90% and 80% targets in the recovery table; the exam asks which method a description matches and which one carries the 15 pound limit.

Piercing valves and recovery bags. A piercing valve (saddle or bullet piercing valve) attaches to sealed system tubing without soldering to give refrigerant access. Solderless piercing valves are for temporary access and must not stay on the appliance, because they leak over time; a solder type piercing valve is the choice when the valve will remain. Recovery bags and passive recovery cylinders are the usual containers for system dependent recovery.

DOT recovery cylinders, labels, and the PT chart check for noncondensables

Recovered refrigerant goes into a refillable recovery cylinder with a DOT specification, gray with a yellow top, never into a disposable (DOT 39) cylinder, which must not be refilled. Fill it to no more than 80% of capacity by weight, keep each refrigerant in its own labeled cylinder; a mixed cylinder cannot be reclaimed. To check for noncondensables such as air or nitrogen, let the cylinder sit until temperature and pressure are stable, then compare the pressure to the PT chart value for that refrigerant. A reading above the chart means noncondensables are present; the check only works when the refrigerant is known and both readings are stable.

Taking the Type 1 exam: providers, open book, retakes

The Type 1 exam is given by EPA-approved certifying organizations, closed book and proctored, with an open book mail in alternative at a higher pass mark.

ESCO Institute and the other EPA-approved certifying organizations

EPA does not write or give the Section 608 exam; it approves certifying organizations, each administering its own version to EPA's specifications. ESCO Institute (escogroup.org) administers its version of the exam and publishes its own preparatory manual; Mainstream Engineering and HVAC Excellence hold the same EPA approval. The 50 questions here are our own bank, verified against 40 CFR Part 82, not ESCO's; this site is not affiliated with ESCO. The EPA 608 certification online guide compares the approved online providers.

Open book mail in option: 84% instead of 72%

Some certifying organizations offer Core and Type 1 as an open book mail in exam without a proctor. Administered open book, the passing threshold rises to 84% (21 of 25 correct) from the 72% (18 of 25) required on the proctored, closed book exam. A Core section passed open book cannot be used toward Universal certification; Core must be taken as a proctored exam for Universal.

Expiry, retakes, and fees. Section 608 certification, including Type 1, never expires: EPA sets no renewal or continuing education requirement (EPA Section 608). If you fail a section, you retake only that section. Each organization sets its own fee: Mainstream Engineering charges $26.95 per attempt and $7.95 per retest, ESCO Institute $25 to $35 per section online proctored, HVAC Excellence $10 to $30 per section in person; the EPA 608 certification cost page lists every fee by organization.

Frequently asked questions about the EPA 608 Type 1 practice test

Is this EPA 608 Type 1 practice test really free?

Yes. All 50 Type 1 questions, scoring, and explanations are free with no signup. A free account unlocks the full 604-question bank with progress tracking; Pro ($14.99 lifetime) adds AI Tutor (1,000 questions/month), drills, and timed simulation.

What is Type 1 certification?

One of four EPA Section 608 categories: small appliances, factory sealed with 5 lbs or less of refrigerant, such as household refrigerators, window AC units, PTACs, and vending machines. Every section is on the EPA 608 practice test hub.

Does Type 1 certification allow me to purchase refrigerant?

Yes. Any Section 608 certification (Type 1, 2, 3, or Universal) allows purchase of refrigerant in containers larger than 2 lbs from EPA-registered distributors.

What refrigerants appear on the Type 1 exam?

Older CFC and HCFC refrigerants such as R-12 and R-22, HFCs such as R-134a, and hydrocarbons such as R-600a (isobutane) and R-290 (propane), which are factory-only substitutes in new household refrigerators and freezers under the EPA SNAP program.